ECMs (Electronically Commutated Motors) manufactured today are the best theyve ever been, and can provide unprecedented airflow delivery to match the required BTUH of a heating and/or cooling system.

There are, however, some serious downsides associated with improper application of these motors in new and existing HVAC systems. Lets take a candid look at the good, bad, and ugly of good and bad application of these great gems of technology:

The Good When a furnace or air handler with an ECM is installed on a good duct, coil, and filtration system with static pressures within proper design parameters, it can perform flawlessly. These systems can deliver precise airflow to match two-speed condenser designs and multi-stage gas furnace firing rates to deliver quiet, draft-free comfort in virtually any configuration.

Additional benefits of these brushless DC motors include low electrical consumption when operating within design TESP (Total External Static Pressure). When installed properly, systems with ECMs can improve dehumidification, reduce register noise, save energy, and provide trouble-free operation.

The Bad In marginal systems with higher-than-design static pressures -- for example a .5in. TESP rated furnace with ECM on a .8in. TESP system -- the motor still may be able to maintain airflow close to design. The tradeoff is higher velocities often cause a noisy system and some coil blow-off. The extra torque often required to overcome the higher statics results in higher electrical consumption. This reduces actual equipment EER, which means your customer wont get the savings of the higher efficiency matchup.

The Ugly Systems with TESPs of 1.0 and higher, which are more typical than many non-performance-based contractors are willing to admit, can eat up to eight times the power they should be using. When this happens, some ECMs will ramp down and drop airflow significantly. Some older ECM motors will overheat and even fail when constantly running in over-amped conditions. Newer models are designed to drop airflow but time will tell on how well they will hold up.

Other consequences of high static installations include noise at the registers from higher air velocities. In extreme cases, filter media can be sucked out of its rack causing filter bypass. In very extreme cases filter media can be pulled into the fan, chopped up and blown through the system causing all sorts of damage.

High velocities and pressures created by ECMs on systems with dirty evaporator coils can also blow moisture off the coil surfaces into the supply ductwork. This can reduce the systems dehumidification capability and cause numerous moisture-related indoor air quality issues.

The Answer These issues can be avoided with good pressure and airflow testing, both before and after equipment is replaced, and on every system you service. When you measure, you know. When you dont measure, youre just guessing that it will turn out OK.

So, what do you measure? The first thing you should do is install test ports on either side of the blower.

Once youve installed the test ports, use a digital or analog manometer with a static pressure tip to measure pressure at each location. TESP is calculated by adding the pressures before and after the fan. Other pressure readings will help you diagnose the cause of high statics but thats for another article.

Once you know your TESP and your fan speed setting look up delivered fan airflow on the manufacturers fan table. If youre replacing or servicing equipment with an ECM, and the TESP exceeds rated capacity, be sure to look up motor amp draw in the manufacturers specifications.

Armed with this information you should do two things: First, alert your customer that their system has a high blood pressure problem that needs to be addressed. Second, diagnose the cause of the high statics and recommend solutions to bring them down to acceptable levels.

Of course, there is more to this in terms of troubleshooting and solving these issues. The bottom line is that while the ECM is a great motor, as the servicing or installing contractor its your responsibility to make sure its application does not cause unintended consequences detrimental to the health and well-being of your customers homes and HVAC systems.

See the original post here:
ECM Motors: The Good, the Bad and the Ugly - Contracting Business

Related Posts
February 9, 2017 at 3:48 am by Mr HomeBuilder
Category: Heating and Cooling - Install